中文

ABB AF Series Contactors | AF09Z / AF26 / AF116 Motor Control

JIAHON is not the authorized distributor of ABB in Taiwan.

ABB AF series contactors | AF09Z / AF26 / AF116 for industrial motor control

AF electronic coil · DC 24 V 1.7 W (AF09Z) · AC/DC universal coil (AF26, AF116) · 9–116 A · 2.2–55 kW

In one line: ABB AF series contactors use an electronic coil — AF09Z (9 A, DC 24 V), AF26 (26 A, 100–250 V) and AF116 (116 A, 100–250 V). The electronic coil draws much less power than a conventional coil, AF26 and AF116 accept AC or DC on the same coil, and built-in surge suppression is included, covering small machines up to 55 kW heavy-duty equipment.

Model comparison

ItemAF09Z-30-10-30AF26-30-00-13AF116-30-00-13
AC-3 rated current9 A (220–240 V @ 60°C)26 A (380–400 V @ 40°C)116 A (380–400 V)
AC-3 motor powerApprox. 2.2 kW @ 400 V11 kW @ 400 V55 kW @ 400 V
Coil voltageDC 24 V (electronic coil, 1.7 W)100–250 V AC/DC universal100–250 V AC/DC universal
Auxiliary contact1NO1NO1NO
Size (W × H × D) / weight45 × 86 × 97 mm / 0.43 kg52 × 100 × 110 mm / approx. 1.2 kgApprox. 85 × 145 × 130 mm / approx. 2.5 kg
Rated insulation voltage690 V AC / 220 V DC690 V AC1000 V AC/DC

AF electronic coil vs. conventional AC coil

ItemABB AF electronic coilConventional AC coil
Coil consumption1.7–3 W (holding)10–50 VA (depending on model)
Coil voltage rangeAF26 / AF116 accept 100–250 V AC/DCUsually AC 110 V or AC 220 V must be specified
HumNone (electronic control)Slight hum on AC supply
PLC drive (AF09Z)DC 24 V 1.7 W, can be driven directlyDC version needed for PLC drive
Spares stockAF26 / AF116 cover AC and DC with one modelSeparate AC and DC spares needed

Which model to choose

  • AF09Z-30-10-30: small PLC-controlled loads up to 2.2 kW, driven directly from DC 24 V; suits densely packed control panels.
  • AF26-30-00-13: mid-size motors up to 11 kW; the 100–250 V AC/DC coil works on 220 V (Taiwan), 110 V (Japan) and 230 V (Europe) supplies.
  • AF116-30-00-13: heavy duty up to 55 kW, such as compressors, large pumps and main drives.
  • Upstream protection: pair with ABB XT1N molded case or S201 miniature circuit breakers.

Related: Siemens 3RT2 / 3TF contactors (7–38 A) · Fuji SC-4-1 contactor (NEO SC series 22 A) · ABB circuit breakers (Tmax XT1N / S200)

Email us for a quote: [email protected]

Back to top