中文

Honeywell C7061A UV Flame Detector (Purple Peeper) | Dynamic Self-Check, R7861

JIAHON is not the authorized distributor of Honeywell in Taiwan.

Honeywell C7061A UV flame detector

Flame supervision is a core safety interlock on industrial boilers, heating furnaces and burners. Conventional flame rods respond slowly and wear out quickly, whereas an ultraviolet (UV) flame detector senses the UV radiation from a flame within milliseconds and, together with a flame safeguard control, gives fast flame-failure protection.

The Honeywell C7061A series is known as the “Purple Peeper” after its purple cast aluminum housing. The C7061A-1012 is the standard model with dynamic self-check: a built-in oscillating shutter periodically blocks the UV tube, and if the shutter or tube fails, the control detects the fault and triggers a safety shutdown.

C7061A-1012 specifications

ItemDetails
ModelC7061A-1012 (discontinued; replacement C7061A1053)
DetectionUltraviolet (UV) flame detection
Self-checkDynamic self-check
AmplifierR7861 Dynamic Self-Check Amplifier
Voltage120 VAC, 50/60 Hz
Ambient temperature−40 to +79°C (−40 to +175°F)
EnclosureNEMA 4
Mounting thread3/4 in NPT
Leadwires96 in (approx. 2.4 m), color-coded
HousingPurple cast aluminum
Pressure rating20 psi (138 kPa)
ApprovalsDepend on model code (Honeywell lists UL Listed, FM Approved, CE and others); please send the full model number

Selecting a version

ModelFeaturesPressure ratingNotes
C7061A (standard)NEMA 4 enclosure20 psiGeneral industrial environments
C7061F (explosion-proof)Explosion-proof housingQuartz window 100 psi (690 kPa)Hazardous area rating depends on full model number (Honeywell data lists ATEX Ex d IIC T6 and UL Class I Groups C, D); please send the full model number

Installation notes: mount the detector so that the conduit opening points about 45° below horizontal to keep condensation out. Aim at the root of the flame, where UV energy peaks, not at the tip. Two detectors can be used in parallel to reduce nuisance shutdowns caused by interference on a single sensor.

Discontinuation: Honeywell has discontinued the C7061A-1012; the direct replacement is the C7061A1053.

Please tell us when requesting a quote: (1) existing model number and quantity (2) installation area (general / hazardous) (3) amplifier used (R7861 or other) (4) whether you need quartz windows or UV tube consumables.

Related: SICK photoelectric sensors · SMC reed switches · SMC control valve accessories

Email us for a quote: [email protected]