中文

SIEMENS QRA10M.C UV Flame Detector | High Sensitivity, for Gas and Oil Burners, IP54

JIAHON is not the authorized distributor of Siemens in Taiwan.

SIEMENS QRA10M.C UV flame detector

The SIEMENS QRA10M.C is a high-sensitivity ultraviolet (UV) flame detector for flame safety supervision on oil and gas burners. After ignition, the detector senses UV radiation from the flame through its UV tube and allows the burner to keep running only while a flame is present; if the flame goes out, the control system shuts off the fuel supply immediately, preventing unburned gas from accumulating.

The QRA10M.C is the high-sensitivity version (M = high sensitivity), for weak flame signals — for example when the detector is far from the flame or its view is partly obstructed. The standard-sensitivity version is the QRA10.C. Both look the same; they differ in the internal UV tube.

QRA series models

ModelSensitivityFlange and clampTerminal coverUV tube
QRA2StandardNoBlackAGR450211310
QRA2 (1)StandardYesBlackAGR450211310
QRA2.9StandardNoBlackAGR450211310
QRA2.9 (9)StandardYesBlackAGR450211310
QRA2MHighNoGreenAGR450240650
QRA2M (1)HighYesGreenAGR450240630
QRA10.CStandard——AGR450211310
QRA10M.CHigh——AGR450240650

QRA10M.C specifications

ItemDetails
PrincipleUltraviolet (UV) flame detection
SensitivityHigh
Flame typesGas flames, blue / yellow oil flames, ignition spark detection
UV tubeAGR450240650 (replaceable)
UV tube lifeApprox. 10,000 operating hours
HousingDie-cast aluminum alloy
ProtectionIP54
Mounting1-inch mounting connector (D), bayonet fixing
Cooling air portSide 1/8-inch connection (for cooling compressed air)
Operating modeIntermittent operation

Compatible burner controls

Control seriesConnection
LFL / LFE1 / LFE10Direct
LGB2 / LGB4With AGQ1 accessory
LMGWith AGQ2 accessory
LME21 / LME22 / LME39With AGQ3 accessory
LMV2 / LMV3 / LMV1Direct

Maintenance note: the UV tube is a wear part. Keeping a spare detector on site helps avoid boiler downtime.

Selection note: if the flame signal is strong (the detector sees the flame directly at short distance), the standard QRA10.C is sufficient. For weak signals (long distance, obstruction), choose the high-sensitivity QRA10M.C. The high-sensitivity type is more susceptible to interference from ignition sparks and welding arcs, so shield it appropriately during installation.

Related: SMC ISE20A / ZSE pressure switches · KEYENCE AP-C30W compound pressure sensor · Panasonic DP-101 pressure sensors

Email us for a quote: [email protected]

Back to top